Waterford Stone: Fire Ratings

Fire resistance ratings are calculated by the percent of solid material in the concrete masonry unit by the actual thickness (in inches) of the units to determine the hourly rating for the type of aggregate used. All Waterford Stone units are 100% solid and are of a limestone material.

FIRE RESISTANCE RATINGS/MINIMUM REQUIRED EQUIVALENT INCHES

Aggregate Type in
The Concrete Masonry Unit
Fire Resistance
0.5 Hr. 0.75 Hr. 1 Hr. 1.5 Hr. 2 Hr. 3 Hr. 4 Hr.
Calcareous or siliceous gravel 2.0 in. 2.4 in. 2.8 in. 3.6 in. 4.2 in. 5.3 in. 6.2 in.

EQUIVALENT THICKNESS OF WATERFORD STONE (IN INCHES)

Nominal Width
(Inches)
Equivalent Thickness
(100% - solid)
Fire Resistance
4 3.625 in. 1.5Â Hr